One of the most common causes of difficulty with 4-20mA systems has to do with current loop error, caused by common -ve or +ve terminals. Some devices, such as PLCs, can accept several 4-20mA inputs, and it is not unusual to find that all – ve terminals are connected to the same point.
Because 4-20mA is a current signal, it can only be properly shared with several devices by connecting them in series, but the common -ve connections in PLCs and other similar devices can upset a series loop. An isolator or two can solve this problem.
Applikationer
Blockdiagram
Mått
Dimension 76,9 x 99,1×6,2 mm
Mounting DIN rail acc. To EN60715
P17G specifications
| Coversion error | +/- 0.2% of the range |
| Thermal error | +/- (0.05% of range / 10°C) |
| Load error | +/- (0.15% of range/100 Ohms) |
| Conversion bandwidth | 70 Hz |
| Isolation | 500V DC - 50Hz 1 minute |
| Warmup time | not required |
| Operating temperature | -10 to 55°C |
| Storage temperature | -25 to +85°C |
| Humidity | <95% non condensing |
| Operating position | any |
| Sustained overload capacity | 40mA |
| Sealing | IP50 (housing) IP20 (electrical) |
| Dimensions | 76.9 x 99.1 x 6.2 mm |
| Weight | 80g |
| Mounting | DIN rail acc. to EN 60715 |
| Analogue input | 4-20mA |
| Input voltage drop | I(in) x R(load out) x 1.25 |
| Output resolution | 0.005mA |
| Output load (Rload) | < 500 Ohms |
| Installation category | III |
| Pollution grade | 2 |