Produktinformation

Serial Data Display for slave and remote applications. Accepts RS232, RS422, RS485 and TTY in ASCII format. Addressable 00 to FF. Able to extract data from complex strings. 300, 600, 1200, 2400, 9600 baud rate. You can also add strings together to give a total value, useful in batching and totalising applications.

The MAXI-INT2-S is a low cost yet highly precise, stable, flexible and easy to use Serial data input slave display, and our top seller, for both display-only and display + output applications. It’s ideal for remote weighing applications and to repeat the reading on another display.
It has a number of useful plug-in options which make it ideal in many control and monitoring applications.
The front panel buttons can be locked, and there is an optional plain front panel with no buttons, which can be put in place of the standard front, after calibration. If you need to be able to read the display in a reflection, for example in a heads-up display system, you can switch it to display a mirrored image.

Interesting fact:
The MAXI-INT2 is the latest release of this well established display, which was first sold 12 years ago. The fact that it is still a popular seller after all these years is proof that it is ‘right’ for the job. We designed it, we build it, we know it inside out, so you can count on us for first class support.

Applikationer

  • Remote weight display
  • Sharing measurements with other operators.
  • Batch totalizing – can add numeric data strings together
  • Serial to analog converter
  • Serial to serial converter – complex to simple format
  • Serial data compared to preset values to create alarms


Blockdiagram

MAXI-INT2-S Block

Mått MAXI-INT2-S

Bezel size:144mm wide x 72mm high. 13mm forward
Depth behind panel:150mm including connectors + cable
Panel cutout:138mm wide x 67,5mm high. +1mm, -0mm

MAXI-INT2-S specifications

ApprovalsProduced to IPC 610 Class 2 Standard

UL ISO9001:2008 QA CERT.
Input connectionsDetachable plug-in screw terminals
Input SignalAccepts RS232 or RS485 input - please specify which you need.

Modes
ASCII: Displays and ASCII character within the limitations of a 7 segment display.
Quant: Displays only numeric ASCII values.
Qa.Tot: Quantity totaliser. Can be used to accumulate weight values, for example after each batch. Uses a contact closure to trigger addition.

Adjustable parameters
Baud rate: 300 to 115200
Data format: 701, 7e1,7n2,801,8e1,8n1,8n2
Termination character: Hex 00 to FF
Reject Characters: counted from termination char.
Addressing00 (wildcard) to F7
Digits6 digits, 20mm high. Legible up to 13 metres away. 10 readings per second. Variable brightness from front panel.
Digit colourRed - standard. Green - optional
Front panel controlsConfiguration, Tare, Reset, Max/Min, Alarms
Power100-240 VAC std, 11-30VDC option. 10VA Power burden, max.
AccuracyNo error, direct copy of input data.
Analogue outputOptional plug-in 16 bit module
Linearity +/- 0.02% of range

0-20/4-20mA into 0 to 500 Ohms
Resolution 0.4uA

0-10V into loads >600 Ohms
Resolution 0.2mV

-10 to+10V into loads >600 Ohms
Resolution 0.4mV

Accuracy 0.1% of range
Stability 50ppm/C

Fully isolated from input and power
Fully scalable with digital precision


Special features
Forward and reverse action possible
Can be set to operate from nett or gross value.
Alarm outputOptional plug-in relay SPST modules
2 Alarms rated 5A 250VAC, SPST
4 Alarms rated 2A 250VAC, SPST
Selectable normally open or normally closed

Optional plug-in relay SPDT modules
2 Alarms rated 5A 250VAC, SPDT

Optional plug-in solid state modules
2 Alarms rated 50V 100mA DC.

Adjustable hysteresis
In-flight compensation facility.
Energise or de-energise on trip

Special features
Adjustable timers to set energise and de-energise delays. Can also be set to pulse for applications needing less than 100% duty cycle.
In-band and out-of-band alarm function.
Manual and automatic in-flight compensation.
Can be set to operate from nett or gross value.
Serial data outputOptional plug-in modules.
RS232
RS485 Addressable
On demand or continuous output.

Special features
Can include time and date with RTC option fitted.
Can be set to operate from nett or gross value.
Logic inputs3 logic inputs, individually configurable for Hold, Reset, Tare, Peak/valley, Nett/Gross, Memory Address

Normally open, NPN or contact closure input to activate.

5V open circuit, 1mA switched current.
Real time clock optionAccuracy better than 2 minutes per year. Allows date and time to be included in serial data, for example for printing time-stamped records.
Automatic summer/winter time correction for Europe and USA

Battery backup to maintain timing whilst switched off. Type = CR1620 3V Lithium
EnvironmentalStorage -20 to +70C
Operating 0 to 50C
Non condensing.
ConnectorsDetachable screw terminals
Bezel size144mm wide x 72mm high. 13mm forward.
Panel cutout138mm wide x 67.5mm high. +1mm, -0mm
Depth behind panel150mm including connectors + cable.
SealingIP54 standard, IP65 with optional SPC4M cover

 